In electrical
signalling A signal is both the process and the result of transmission of data over some media accomplished by embedding some variation. Signals are important in multiple subject fields including signal processing, information theory and biology. In ...
an analog current loop is used where a device must be monitored or controlled remotely over a pair of conductors. Only one current level can be present at any time. A major application of current loops is the industry
de facto standard A ''de facto'' standard is a custom or convention that is commonly used even though its use is not required. is a Latin phrase (literally " of fact"), here meaning "in practice but not necessarily ordained by law" or "in practice or actuality, ...
4–20 mA current loop for
process control Industrial process control (IPC) or simply process control is a system used in modern manufacturing which uses the principles of control theory and physical industrial control systems to monitor, control and optimize continuous Industrial processe ...
applications, where they are extensively used to carry signals from process
instrumentation Instrumentation is a collective term for measuring instruments, used for indicating, measuring, and recording physical quantities. It is also a field of study about the art and science about making measurement instruments, involving the related ...
to proportional–integral–derivative (PID) controllers, supervisory control and data acquisition (SCADA) systems, and programmable logic controllers (PLCs). They are also used to transmit controller outputs to the modulating field devices such as
control valves A control valve is a valve used to control fluid flow by varying the size of the flow passage as directed by a signal from a controller. This enables the direct control of flow rate and the consequential control of process quantities such as press ...
. These loops have the advantages of simplicity and noise immunity, and have a large international user and equipment supplier base. Some 4–20 mA field devices can be powered by the current loop itself, removing the need for separate power supplies, and the "smart" Highway Addressable Remote Transducer (HART) Protocol uses the loop for communications between field devices and controllers. Various
automation protocols This is a list of communication protocols used for the automation of processes (industrial or otherwise), such as for building automation, power-system automation, automatic meter reading, and vehicular automation. Process automation protocols * A ...
may replace analog current loops, but 4–20 mA is still a principal industrial standard.


Process control 4–20 mA loops

In industrial
process control Industrial process control (IPC) or simply process control is a system used in modern manufacturing which uses the principles of control theory and physical industrial control systems to monitor, control and optimize continuous Industrial processe ...
,
analog Analog or analogue may refer to: Computing and electronics * Analog signal, in which information is encoded in a continuous variable ** Analog device, an apparatus that operates on analog signals *** Analog electronics, circuits which use analog ...
4–20 mA current loops are commonly used for electronic signalling, with the two values of 4 and 20 mA representing 0–100% of the range of measurement or control. These loops are used both for carrying sensor information from field instrumentation and carrying control signals to the process modulating devices, such as a valve. The key advantages of the current loop are: * The loop can often power the remote device, with power supplied by the controller, thus removing need for power cabling. Many instrumentation manufacturers produce 4–20 mA sensors which are "loop powered". * The "live" or "elevated" zero of 4 mA allows powering of the device even with no process signal output from the field transmitter. * The accuracy of the signal is not affected by voltage drop in the interconnecting wiring. * It has high noise immunity, as it is low-impedance circuit, usually through twisted-pair conductors. * It is self-monitoring; currents less than 3.8 mA or more than 20.5 mA are taken to indicate a fault. * It can be carried over long cables up to the limit of the resistance for the voltage used. * Inline displays can be inserted and powered by the loop, as long as total allowable loop resistance is not exceeded. * Easy conversion to voltage using a resistor. * Loop-powered "I to P" (current to pressure) converters can convert the 4–20 mA signal to a 3–15 psi pneumatic output for control valves, allowing easy integration of 4–20 mA signals into existing pneumatic plant. Field instrumentation measurements include
pressure Pressure (symbol: ''p'' or ''P'') is the force applied perpendicular to the surface of an object per unit area over which that force is distributed. Gauge pressure (also spelled ''gage'' pressure)The preferred spelling varies by country and eve ...
,
temperature Temperature is a physical quantity that quantitatively expresses the attribute of hotness or coldness. Temperature is measurement, measured with a thermometer. It reflects the average kinetic energy of the vibrating and colliding atoms making ...
, level, flow, pH or other process variables. A current loop can also be used to control a valve positioner or other output
actuator An actuator is a machine element, component of a machine that produces force, torque, or Displacement (geometry), displacement, when an electrical, Pneumatics, pneumatic or Hydraulic fluid, hydraulic input is supplied to it in a system (called an ...
. Since input terminals of instruments may have one side of the current loop input tied to the chassis ground (earth), analog isolators may be required when connecting several instruments in series. The relationship between current value and process variable measurement is set by calibration, which assigns different ranges of engineering units to the span between 4 and 20 mA. The mapping between engineering units and current can be inverted, so that 4 mA represents the maximum and 20 mA the minimum.


Active and passive devices

Depending on the source of current for the loop, devices may be classified as ''active'' (supplying or "sourcing" power) or ''passive'' (relying on or "sinking" loop power). For example, a
chart recorder A chart recorder is an electromechanical device that records an electrical or mechanical input trend onto a piece of paper (the chart). Chart recorders may record several inputs using different color pens and may record onto strip charts or circu ...
may provide loop power to a pressure transmitter. The pressure transmitter modulates the current on the loop to send the signal to the strip chart recorder, but does not in itself supply power to the loop and so is passive. Another loop may contain two passive chart recorders, a passive pressure transmitter, and a 24 V battery (the battery is the active device). Note that a ''4-wire'' instrument has a power-supply input separate from the current loop. Panel mount displays and chart recorders are commonly termed "indicator devices" or "process monitors". Several passive indicator devices may be connected in series, but a loop must have only one transmitter device and only one power source (active device).


Evolution of analogue control signals

The 4–20 mA convention was born in the 1950s out of the earlier highly successful 3–15 psi pneumatic control signal standard, when electronics became cheap and reliable enough to emulate the older standard electrically. The 3–15 psi standard had the same features of being able to power some remote devices, and have a "live" zero. However, the 4–20 mA standard was better suited to the electronic controllers being developed at the time. The transition was gradual and has extended into the 21st century, due to the huge installed base of 3–15 psi devices. As the operation of pneumatic valves over motorised valves has many cost and reliability advantages, pneumatic actuation is still an industry standard. To allow the construction of hybrid systems, where the 4–20 mA is generated by the controller, but allows the use of pneumatic valves, a range of current to pressure (I to P) converters are available from manufacturers. These are usually local to the control valve and convert 4–20 mA to 3–15 psi (or 0.2–1.0 bar). This signal is then fed to the valve actuator or, more commonly, a pneumatic positioner. The positioner is a dedicated controller which has a mechanical linkage to the actuator movement. This ensures that problems of friction are overcome and the valve control element moves to the desired position. It also allows the use of higher air pressures for valve actuation. With the development of cheap industrial micro-processors, "smart" valve positioners have become available since the mid-1980s and are very popular for new installations. These include an I to P converter, plus valve position and condition monitoring. These latter are fed back over the current loop to the controller, using protocols such as
HART Hart often refers to: * Hart (deer) * Hart (surname) Hart may also refer to: Organizations * Hart Racing Engines, a former Formula One engine manufacturer * Hart Skis, US ski manufacturer * Hart Stores, a Canadian chain of department store ...
.


Long circuits

Analog current loops were historically occasionally carried between buildings by
dry pair A dry loop is an unconditioned leased pair of telephone line from a telephone company. The pair does not provide dial tone or battery (continuous electric potential), as opposed to a wet pair, a line usually without dial tone but with battery. ...
s in telephone cables leased from the local telephone company. 4–20 mA loops were more common in the days of analog telephony. These circuits require end-to-end direct current (DC) continuity, and unless a dedicated wire pair was hardwired, their use ceased with the introduction of semiconductor switching. DC continuity is not available over a microwave radio, optical fibre, or a multiplexed telephone circuit connection. Basic DC circuit theory shows that the current is the same all along the line. It was common to see 4–20 mA circuits that had loop lengths in miles or circuits working over telephone cable pairs that were longer than ten thousand feet end-to-end. There are still legacy systems in place using this technology. In
Bell System The Bell System was a system of telecommunication companies, led by the Bell Telephone Company and later by the AT&T Corporation, American Telephone and Telegraph Company (AT&T), that dominated the telephone services industry in North America fo ...
circuits, voltages up to 125 VDC were employed.


Discrete control

Discrete control functions can be represented by discrete levels of current sent over a loop. This would allow multiple control functions to be operated over a single pair of wires. Currents required for a specific function vary from one application or manufacturer to another. There is no specific current that is tied to a single meaning. It is almost universal that 0 mA indicates the circuit has failed. In the case of a fire alarm, 6 mA could be normal, 15 mA could mean a fire has been detected, and 0 mA would produce a trouble indication, telling the monitoring site the alarm circuit had failed. Some devices, such as
two-way radio A two-way radio is a radio transceiver (a radio that can both transmit and receive radio waves), which is used for bidirectional person-to-person voice communication with other users with similar radios, in contrast to a broadcast receiver, whi ...
remote control consoles, can reverse the polarity of currents and can multiplex audio onto a DC current. These devices can be employed for any remote control need a designer might imagine. For example, a current loop could actuate an evacuation siren or command synchronized
traffic signals Traffic lights, traffic signals, or stoplights – also known as robots in South Africa, Zambia, and Namibia – are signaling devices positioned at intersection (road), road intersections, pedestrian crossings, and other locations in order t ...
.


Two-way radio use

Current loop circuits are one possible way used to control radio
base station Base station (or base radio station, BS) is – according to the International Telecommunication Union's (ITU) Radio Regulations (RR) – a " land station in the land mobile service." A base station is called '' node B'' in 3G, '' eNB'' in L ...
s at distant sites. The two-way radio industry calls this type of remote control DC remote. This name comes from the need for DC circuit continuity between the control point and the radio
base station Base station (or base radio station, BS) is – according to the International Telecommunication Union's (ITU) Radio Regulations (RR) – a " land station in the land mobile service." A base station is called '' node B'' in 3G, '' eNB'' in L ...
. A current loop remote control saves the cost of extra pairs of wires between the operating point and the radio transceiver. Some equipment, such as the Motorola MSF-5000 base station, uses currents below 4 mA for some functions. An alternative type, the
tone remote Remote controls are used any time a two-way radio base station is located away from the desk or office where communication originates. For example, a dispatch center for taxicabs may have an office downtown but have a base station on a distan ...
, is more complex but requires only an audio path between control point and base station. (The patent does not describe this tone remote but confirms the use of the phrase to describe this system of signaling.) For example, a
taxi A taxi, also known as a taxicab or simply a cab, is a type of vehicle for hire with a Driving, driver, used by a single passenger or small group of passengers, often for a non-shared ride. A taxicab conveys passengers between locations of thei ...
dispatch base station might be physically located on the rooftop of an eight-story building. The taxi company office might be in the basement of a different building nearby. The office would have a remote control unit that would operate the taxi company base station over a current loop circuit. The circuit would normally be over a telephone line or similar wiring. Control function currents come from the remote control console at the dispatch office end of a circuit. In two-way radio use, an idle circuit would normally have no current present. In
two-way radio A two-way radio is a radio transceiver (a radio that can both transmit and receive radio waves), which is used for bidirectional person-to-person voice communication with other users with similar radios, in contrast to a broadcast receiver, whi ...
use, radio manufacturers use different currents for specific functions. Polarities are changed to get more possible functions over a single circuit. For example, imagine one possible scheme where the presence of these currents cause the base station to change state: * no current means ''receive on channel 1'', (the default). * +6 mA might mean ''transmit on channel 1'' * −6 mA might mean ''stay in receive mode but switch to channel 2''. So long as the −6 mA current were present, the remote base station would continue to receive on channel 2. * −12 mA might command the base station to ''transmit on channel 2''. This circuit is polarity-sensitive. If a telephone company cable splicer accidentally reversed the conductors, selecting channel 2 would lock the transmitter on. Each current level could close a set of contacts, or operate solid-state logic, at the other end of the circuit. That contact closure caused a change of state on the controlled device. Some remote control equipment could have options set to allow compatibility between manufacturers. That is, a base station that was configured to transmit with a +18 mA current could have options changed to (instead) make it transmit when +6 mA was present. In two-way radio use, AC signals were also present on the circuit pair. If the base station were idle, receive audio would be sent over the line from the base station to the dispatch office. In the presence of a transmit command current, the remote control console would send audio to be transmitted. The voice of the user in the dispatch office would be modulated and superimposed over the DC current that caused the transmitter to operate.


See also

*
Current source A current source is an electronic circuit that delivers or absorbs an electric current which is independent of the voltage across it. A current source is the dual of a voltage source. The term ''current sink'' is sometimes used for sources fed ...
– a current loop transmitter *
Current-to-voltage converter In electronics, a transimpedance amplifier (TIA) is a current to voltage converter, almost exclusively implemented with one or more operational amplifiers. The TIA can be used to amplify the current output of Geiger–Müller tubes, photo multipli ...
*
Highway Addressable Remote Transducer Protocol The HART Communication Protocol (Highway Addressable Remote Transducer) is a hybrid analog+digital industrial automation open protocol. Its most notable advantage is that it can communicate over legacy 4–20 mA analog instrumentation current loop ...
*
NAMUR Namur (; ; ) is a city and municipality in Wallonia, Belgium. It is the capital both of the province of Namur and of Wallonia, hosting the Parliament of Wallonia, the Government of Wallonia and its administration. Namur stands at the confl ...
German industry standards body defining fault levels for 4–20 mA *
Piping and instrumentation diagram A Piping and Instrumentation Diagram (P&ID) is a detailed diagram in the process industry which shows process equipment together with the instrumentation and control devices. It is also called as mechanical flow diagram (MFD). Superordinate to t ...
Gives the control scheme and associated piping and vessels.


References


Further reading

* Lipták, Béla G. ''Instrumentation Engineers' Handbook. Process Measurement and Analysis''. CRC Press. 2003. HB.


External links


Fundamentals, System Design, and Setup for the 4 to 20 mA Current Loop
* {{cite web , url=http://www.murata-ps.com/data/meters/dms-an20.pdf , title=4–20 mA Current Loop Primer , access-date=10 September 2017

!-- 4–20 mA here and/or new title: MEASUREMENT SPECIALTIES -->


How to read current loop using arduino

Types of 4-20 mA Current Loop
Communication circuits Control engineering Electronics standards Industrial automation Analog communication interfaces